6.3 Selecting Cables

Cable requirements:

☐ Conductor material: copper
☐ Conductor structure: solid wire, coarse stranded wire, or fine stranded wire
☐ The cable must be approved for 167°F (75°C).
☐ Maximum wire size: 4 AWG

Minimum wire sizes

• Make sure that the general cable requirements are adhered to.
• Make sure that minimum and maximum wire sizes are adhered to.

If you connect a Sunny Island 5048-US without labeling "Smartformer compatible" on the original
packaging, observe the following procedure:

• Select a wire size of 6 AWG for the AC 1 connection cable of the Sunny Island.
• Fuse the AC 1 connection cable of the Sunny Island outside of the Smartformer. Use a 60 A

miniature circuit-breaker, for example.

• In order to avoid excessive tripping of the 60 A miniature circuit-breaker, limit the rated power

of the loads to 5.8 kW.

Components for connection

Minimum wire size

Loads

6 AWG

PV plant with miniature circuit-breaker 25 A

10 AWG

PV plant with miniature circuit-breaker 50 A

6 AWG

Generator or power distribution grid

6 AWG

Sunny Island: AC 1 terminal

4 AWG*

* Valid for Sunny Island 4548-US / 6048-US and for Sunny Island 5048-US with labeling "Smartformer compatible" on the

original packaging

Sunny Island: AC 2 terminal

6 AWG