11.9 Torque Values and Cable Sizes
*see National Electrical Code
®
, 310.16
in-lb.
Nm
Wire size
Sunny Boy
AC terminal block
40
4.5
6 to 2 AWG (16 to 35 mm²)
copper wire, rated for 194°F
(90°C)*
DC terminal block
40
4.5
8 to 2 AWG (10 to 35 mm²)
copper wire, rated for 194°F
(90°C) *
Attachment to the wall mounting
bracket
44
5
-
Enclosure lid
53
6
-
DC Disconnect
AC terminal block
40
4.5
6 to 2 AWG (16 to 35 mm²)
copper wire, rated for 194°F
(90°C)*
DC terminal block
40
4.5
8 to 2 AWG (10 to 35 mm²)
copper wire, rated for 194°F
(90°C) *
Terminal block grounding
conductor
40
4.5
8 to 2 AWG (10 to 35 mm²)
copper wire, rated for 194°F
(90°C) *
Attachment to the wall mounting
bracket
44
5
-
Enclosure lid
44
5
-