5 sunny boy 10000tl-us, Sunny boy 10000tl-us – SMA SB 6000TL‑US Installation User Manual
Page 80

11 Technical Data
SMA America, LLC
80
SB6-11TL-US-IA-en-13
Installation Manual
11.5 Sunny Boy 10000TL-US
PV Array Connection
Grid Connection
Maximum DC power
10,350 W
Maximum DC voltage
600 V
Minimum DC voltage at 208 V AC
300 V
Minimum DC voltage at 240 V AC
345 V
DC nominal voltage at 208 V AC
345 V
DC nominal voltage at 240 V AC
379 V
DC start voltage
360 V
MPP voltage range at 208 V AC
300 V to 480 V
MPP voltage range at 240 V AC
345 V to 480 V
Maximum DC input current at 208 V AC
35 A
Maximum DC input current at 240 V AC
30 A
Number of MPP trackers
1 (OptiTrac)
AC nominal power
10,000 W
Maximum AC power
10,000 W
Reduced power output at 140°F (60°C)
8,000 W
Maximum AC current at 208 V AC
49 A
Maximum AC current at 240 V AC
48 A
Maximum AC reverse current
0 A
Maximum AC fuse size
60 A
AC nominal voltage
208 V/240 V
AC voltage range at 208 V AC
183 V to 229 V
AC voltage range at 240 V AC
211 V to 264 V
AC nominal frequency
60 Hz
AC nominal frequency range
59.3 Hz to 60.5 Hz
Power factor at nominal power
1
Total harmonic factor
< 4%
AC connection/Power Balancing
Two Phases / ✓
Ground fault monitoring (R-Iso)
Yes
Power consumption nighttime
≤ 0.25 W