beautypg.com

SMA SB 6000TL‑US Installation User Manual

Page 83

background image

SMA America, LLC

11  Technical Data

Installation Manual

SB6-11TL-US-IA-en-13

83

Grid Connection

Protection Devices

General Data

AC nominal power

11,000 W

Maximum AC power

11,000 W

Reduced power output at 140 °F (60 °C)

8,000 W

Maximum AC current at 240 V AC

48.6 A

Maximum AC reverse current

0 A

Maximum AC fuse size

60 A

AC nominal voltage

240 V

AC voltage range at 240 V AC

211 V to 264 V

AC nominal frequency

60 Hz

AC nominal frequency range

59.3 Hz to 60.5 Hz

Power factor at nominal power

1

Total harmonic factor

< 4%

AC connection/Power Balancing

Two Phases / ✓

Ground fault monitoring (R-Iso)

Yes

Power consumption nighttime

≤ 0.25 W

DC reverse polarity protection

Short-circuit diode

AC short-circuit current capability

Software-controlled

AC overcurrent protection

Current-controlled

Grid monitoring

SMA Grid Guard

Topology

Transformerless

Cooling concept

OptiCool

Protection class

NEMA 3R

Optional communication interfaces

RS485/wireless (Bluetooth)

DC connection

Screw terminals

AC connection

Screw terminals