SMA SB 6000TL‑US Installation User Manual
Page 73

SMA America, LLC
11 Technical Data
Installation Manual
SB6-11TL-US-IA-en-13
73
Grid Connection
Protection Devices
General Data
AC nominal power
7,000 W
Maximum AC power
7,000 W
Reduced power output at 140°F (60°C)
7,000 W
Maximum AC current at 208 V AC
39 A
Maximum AC current at 240 V AC
34 A
Maximum AC reverse current
0 A
Maximum AC fuse size
45 A
AC nominal voltage
208 V/240 V
AC voltage range at 208 V AC
183 V to 229 V
AC voltage range at 240 V AC
211 V to 264 V
AC nominal frequency
60 Hz
AC nominal frequency range
59.3 Hz to 60.5 Hz
Power factor at nominal power
1
Total harmonic factor
< 4%
AC connection/Power Balancing
Two Phases / ✓
Ground fault monitoring (R-Iso)
Yes
Power consumption nighttime
≤ 0.25 W
DC reverse polarity protection
Short-circuit diode
AC short-circuit current capability
Software-controlled
AC overcurrent protection
Current-controlled
Grid monitoring
SMA Grid Guard 2
Topology
Transformerless H5
Cooling concept
OptiCool
Protection class
NEMA 3R
Optional communication interfaces
RS485/wireless (Bluetooth)
DC connection
Screw terminals
AC connection
Screw terminals