5  Electrical Connection

SMA America, LLC

40

SB6-11TL-US-IA-en-13

Installation Manual

5.5.1 DC Cable Requirements

DC cabling to the Combiner Box

Use copper wire that is rated for 10 to 6 AWG (6 to 16 mm²) and 194°F (90°C) (National

Electrical Code

®

690.35).

DC cabling Between the Combiner Box and the Inverter

Use copper wire that is rated for min. 8 AWG (10 mm²) and 194°F (90°C) (National Electrical

Code

®

690.35).

5.5.2 Connecting the DC Cables in the DC Disconnect

1. Lay a conduit from the Sunny Boy Combiner Box to the DC Disconnect

(see Section 5.2 "Inserting the Cables in the DC Disconnect", page 31).

2. Open the DC Disconnect as described in Section 8.3 "Opening the DC Disconnect", page 58.
3. Pull the DC cable from the Sunny Boy Combiner Box through the conduit into the DC Disconnect.

4. Connect the grounding conductor to terminal (B)

for the grounding conductor.

If necessary:

Connect the grounding cable of the PV frame to
terminal (A) for the grounding conductor.

Only use solid wire or stranded wire

• Use the free of charge "Sunny Design" at www.SMA-America.com to design your PV

plant.

Open terminals fully before insertion of the cables.