5  Electrical Connection

SMA America, LLC

34

SB6-11TL-US-IA-en-13

Installation Manual

System configuration

The following table shows the possible system configurations for the inverter types:

*not SB 11000TLUS-12

AC cable requirements

The cable must be dimensioned in accordance with the local and national directives for the
dimensioning of cables. The requirements for the minimum conductor cross-section derive from these
directives. Influencing factors for cable dimensioning are, among others, the following: nominal AC
current, type of cable, cable length, routing method, cable bundling, ambient temperature and
maximum desired line losses.

Inverter type

Voltage

208 V WYE

240 V Split Phase

SB xxxxTLUS-10

SB xxxxTLUS-12

✓ *

A neutral conductor must be connected to the inverter in either grid situation.

Only use solid wire or stranded wire

• Do not use fine-wire strands.

Ambient temperature
The higher the ambient temperature, the higher the power losses.

• Use cables with large cable cross-sections in installation sites with high ambient

temperatures.

Routing method
The cables heat up during operation. If there are several cables in a conduit, the temperature
of all cables increases.

• Use cables with a large cross-section if you lay several cables in one conduit.

Position

Name

Value

A

Conductor cross-section

6 to 2 AWG (16 to 35 mm²)

B

Stripping insulation

3

4

in.(18 mm)