4  Mounting

Installation Manual

SB6-11TL-US-IA-en-13

21

☐ Observe recommended clearances to walls, other inverters or other objects. As a result,

sufficient heat dissipation is ensured.

☐ If several inverters are mounted in areas with high ambient temperatures, increase the

clearances and ensure a sufficient fresh-air supply. Thus, you will prevent the inverter power
from being reduced due to too high temperatures.

Recommended clearances

The National Electrical Code

®

may stipulate greater clearances (see National Electrical

Code

®

, Section 110.26). Installations in Canada must be carried out in accordance with

the applicable Canadian standards.

Position

Clearance

Top

12 in. (300 mm)

Bottom

12 in. (300 mm)

Left

12 in. (300 mm)

Right

12 in. (300 mm)

Front

2 in. (50 mm)

If the Sunny Boy is installed outdoors

• Observe minimum clearance to the ground of 36 in. (900 mm).

12 in.

12 in.

2 in.

12 in.

12 in.