beautypg.com

8 tripping limits and tripping times, Tripping limits and tripping times – SMA SB 6000TL‑US Installation User Manual

Page 86

background image

11  Technical Data

SMA America, LLC

86

SB6-11TL-US-IA-en-13

Installation Manual

11.8 Tripping Limits and Tripping Times

Measurement accuracy

• Tripping limit accuracy: ±2 % of nominal grid voltage
• Tripping time accuracy: ±1 % of nominal tripping time
• Tripping frequency accuracy: ±0.05 Hz

Nominal

frequency

Tripping limit

Tripping frequencies

Tripping times

60 Hz

> 60 5 Hz

60.45 Hz to 60.55 Hz

max. 0.1602 s

< 57.0 Hz to 59.8 Hz

(Standard 59.3 Hz)

56.95 Hz to 59.85 Hz

(Standard

59.25 Hz to 59.35 Hz)

adjustable,

0.16 s to 300 s

(Standard max. 0.1602 s)

< 57.0 Hz

56.95 Hz to 57.05 Hz

max. 0.1602 s

Voltage

Tripping limit -

tripping voltages

Conductor-

neutral conductor

Tripping voltage -

conductor-

conductor

Tripping times

208 V

50%

57.6 to 62.4 V

99.8 to 108.2 V

max. 0.1602 s

88%

103.2 to 108.0 V 178.9 to 187.2 V

max. 2.002 s

110%

129.6 to 134.4 V 224.6 to 233.0 V

max. 1.001 s

120%

141.6 to 146.4 V 245.4 to 253.8 V

max. 0.1602 s

240 V

50%

57.6 to 62.4 V

115.2 to 124.8 V

max. 0.1602 s

88%

103.2 to 108.0 V 206.4 to 216.0 V

max. 2.002 s

110%

129.6 to 134.4 V 259.2 to 268.8 V

max. 1.001 s

120%

141.6 to 146.4 V 283.2 to 292.8 V

max. 0.1602 s