beautypg.com

4 dc disconnect, 5 climatic conditions, 6 features – SMA SB 3000TL-US Installation User Manual

Page 91: 4 dc disconnect 13.5 climatic conditions

background image

SMA America, LLC

13  Technical Data

Installation Manual

SB3-5TLUS22-IA-en-16

91

13.4 DC Disconnect

13.5 Climatic Conditions

According to IEC 60721-3-4, installation type C, class 4K4H

According to IEC 60721-3-2, transport type E, class 2K3

13.6 Features

Maximum rated switching current per string input

20 A

Maximum switching voltage

600 V

Degree of protection

NEMA 3R

Extended temperature range

− 40°F to +140°F ( − 40°C to +60°C)

Extended humidity range

0% to 100%

Extended air pressure range

79.5 kPa to 106 kPa

Temperature range

− 40°F to +140°F ( − 40°C to +60°C)

DC connection

Screw terminal

AC connection

Spring-cage terminal

Display

LC graphic display

RS485, galvanically isolated

optional

Speedwire with Webconnect function

optional

Fan retrofit kit

optional

SPS module

optional*

* only with a corresponding order, no retrofitting possible