2 protective devices – SMA SB 3000TL-US Installation User Manual
Page 89

SMA America, LLC
13 Technical Data
Installation Manual
SB3-5TLUS22-IA-en-16
89
AC Output
Efficiency
13.2 Protective Devices
Rated power at 208 V, 60 Hz
6,650 W
Rated power at 240 V, 60 Hz
7,680 W
Maximum apparent power at 208 V, 60 Hz
6,650 VA
Maximum apparent power at 240 V, 60 Hz
7,680 VA
Nominal AC voltage
208 V / 240 V
AC voltage range at 208 V nominal
183 V to 229 V
AC voltage range at 240 V nominal
211 V to 264 V
Nominal AC current at 208 V
32 A
Nominal AC current at 240 V
32 A
Maximum output current
32 A
Maximum overcurrent protection
40 A
Total harmonic distortion
≤ 4%
Nominal AC frequency
60 Hz
AC frequency range at 60 Hz nominal
59.3 Hz to 60.5 Hz
Power factor at rated power
1
Connection conductor
2
Output connections
L1, L2, N, PE
Maximum efficiency, η
max
97.4%*
* preliminary
CEC efficiency, η
CEC
at 208 V AC nominal
96.5%*
CEC efficiency, η
CEC
at 240 V AC nominal
97.0%*
DC reverse-polarity protection
Short-circuit diode
Input-side disconnection device
DC Disconnect
DC overvoltage protection
Varistors
AC short-circuit current capability
Current control
Grid monitoring
SMA Grid Guard X
Ground-fault monitoring
Insulation monitoring: R
iso
≥ 600 kΩ
All-pole sensitive residual-current monitoring unit
Present
DC arc-fault circuit interrupter
DC AFCI