11  Troubleshooting

Installation Manual

SB3-5TLUS22-IA-en-16

71

11.3 Cleaning the Inverter

• If the cooling fins on the rear of the enclosure are dirty, clean them with a soft brush.
• If the air ducts on the top of the inverter are dirty, clean them with a soft brush.

11.4 Cleaning the Fan

The SB 6000TL-US, SB 7000TL-US and SB 7700TL-US are equipped with a fan as standard. You can
dismantle the fan for cleaning, as described in the following sections.

11.4.1 Sunny Boy 3000/3800/4000/5000/6000TL-US

Disassembling the Fan

1. Disconnect the inverter from any voltage sources (see Section 10 "Disconnecting the Inverter

from Voltage Sources", page 55).

2. Loosen the screws of the lower enclosure lid and remove the enclosure lid.
3. Wait for the fan to stop rotating.

9005

Changing grid param.
not possible
Ensure DC supply

This error can have the following causes:

• The selected rotary switch setting for the

country configuration is not programmed.

• The parameters to be changed are

protected.

• The DC voltage at the DC input is not

sufficient to run the main CPU.

Corrective measures:

• Check the settings of the rotary switches (see

Section 7.1.2 "Changing the Country Data
Set and the Display Language", page 49).

• Enter the SMA Grid Guard code.
• Ensure sufficient DC voltage (green LED

lights up or flashes).

Damage to the display due to the use of cleaning agents

• If the inverter is dirty, clean the enclosure lid, the display, and the LEDs using only clean water

and a cloth.

Event number

Display message

Cause and corrective measures