10  Disconnecting the Inverter from Voltage Sources

SMA America, LLC

56

SB3-5TLUS22-IA-en-16

Installation Manual

7. Ensure that no voltage is present on the AC connecting terminal plate using a suitable measuring

device. Insert the test probe in each round opening of the terminal:

• Ensure that no voltage is present between

L1 and N.

• Ensure that no voltage is present between L1 and

the equipment grounding conductor.

• Ensure that no voltage is present between

L2 and N.

6.

Damage to the inverter due to electrostatic discharge
The internal components of the inverter can be irreparably damaged by electrostatic discharge.

• Ground yourself before touching any components.