11  Troubleshooting

SMA America, LLC

70

SB3-5TLUS22-IA-en-16

Installation Manual

8801 to 8803

No display

This error message can have 3 causes but the
inverter continues to feed into the utility grid.
The ambient temperature is lower than ‒13°F
(‒25°C). The display switched off for protection.
The inverter cannot identify the display type.
No display is connected to the inverter or the
connection is defective.
Corrective measures:

• If the display switched off due to the ambient

temperature being too low, wait until the
ambient temperature is above ‒13°F
(‒25°C).

• If the ambient temperature is above ‒13°F

(‒25°C), contact the SMA Service Line.

9002

Grid guard code
invalid

The SMA Grid Guard code entered is incorrect.
The parameters are still protected and cannot be
changed.
Corrective measures:

• Enter the correct SMA Grid Guard code.

9003

Grid param. locked

The parameters are now locked. The parameters
cannot be changed.
Corrective measures:

• Unlock the parameters with the

SMA Grid Guard code.

Event number

Display message

Cause and corrective measures