11  Troubleshooting

Installation Manual

SB3-5TLUS22-IA-en-16

67

7105

Param. setting failed

Parameters cannot be set via the SD card. The
inverter continues feeding power into the grid.
Corrective measures:

• Check the parameters for valid values.
• Ensure change rights via SMA Grid Guard

code.

7106

Update file defect.

The update file is defective. The update failed.
The inverter continues feeding power into the
grid.
Corrective measures:

• Re-format the SD card.
• Re-save the files to the SD card.

7110

No update file found

No new update file was found on the SD card.
The update failed. The inverter continues feeding
power into the grid.
Corrective measures:

• Copy the update file into the SD card

drive:\UPDATE directory.

7201 to 7202

Data stor. not poss.

Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:

• If this error occurs frequently, contact the

SMA Service Line.

7303

Update main CPU
failed

Internal device fault. The inverter continues
feeding power into the grid. In very rare cases,
the firmware is damaged and the inverter
interrupts the feed-in.
Corrective measures:

• Contact the SMA Service Line.

7305

Update RS485I
module failed

Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:

• Re-try update.
• If this error occurs again, contact the

SMA Service Line.

Event number

Display message

Cause and corrective measures