11  Troubleshooting

SMA America, LLC

68

SB3-5TLUS22-IA-en-16

Installation Manual

7311

Update language table
failed

Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:

• Re-try update.
• If this error occurs again, contact the

SMA Service Line.

7316

Update Speedwire
module failed

Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:

• Re-try update.
• If this error occurs again, contact the

SMA Service Line.

7326

Webconnect update
unsuccessful

Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:

• Re-try update.
• If this error occurs again, contact the

SMA Service Line.

7508

External fan fault

The fan is contaminated or defective. The inverter
may reduce its power due to overheating. The
inverter continues feeding power into the grid.
Corrective measures:

• Clean the fan
• Replace the fan.

7701 to 7712

Self diagnosis
Interference device

The cause must be determined by the
SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.