3 general data – SMA SB 3000TL-US Installation User Manual
Page 90

13 Technical Data
SMA America, LLC
90
SB3-5TLUS22-IA-en-16
Installation Manual
13.3 General Data
Width x height x depth, inverter
19
5
⁄
16
in. x 20
1
⁄
2
in. x 7
5
⁄
16
in.
(490 mm x 519 mm x 185 mm)
Width x height x depth, DC Disconnect
7
13
⁄
32
in. x 11
45
⁄
64
in. x 7
1
⁄
2
in.
(187 mm x 297 mm x 190 mm)
Weight inverter
52.9 lb (24 kg)
Weight DC Disconnect
4.4 lb (2 kg)
Length x width x height of the inverter packaging
24
5
⁄
16
in. x 23
1
⁄
2
in. x 10
1
⁄
2
in.
(617 mm x 597 mm x 266 mm)
Length x width x height of the DC Disconnect
packaging
14
39
⁄
64
in. x 9
13
⁄
32
in. x 11 in.
(370 mm x 240 mm x 280 mm)
Transport weight inverter
59.5 lb (27 kg)
Transport weight DC Disconnect
6.6 lb (3 kg)
Climatic category according to IEC 60721-3-4
4K4H
Operating temperature range
− 40°F to +140°F ( − 40°C to +60°C)*
* Sunny Boy 6000TL-US, 7000TL-US and 7700TL-US: − 22°F to +140°F ( − 30°C to +60°C)
Maximum permissible value for relative humidity,
non-condensing
100%
Maximum operating altitude above
Mean Sea Level
3,000 m
Noise emission, typical
≤ 25 dB(A)
Power loss in night mode
< 1 W
Topology
Transformerless
Cooling concept
Convection
Fan connection
designed for safe disconnection in accordance
with DIN EN 50178:1998-04
(until 2013 replaced by DIN EN 62109-1)
Electronics degree of protection
NEMA 3R
Protection class
I
Overvoltage category
IV
Approvals, as at September 2013
UL 1741,
UL 1699B,
IEEE 929-2000,
IEEE 1547,
Canadian Electrical Code
®
CSA C22.2 N0. 107.1-01
Grid configurations
208/120 V Wye,
120/240 V Split-phase