beautypg.com

Emerson FM-3 User Manual

Page 10

background image

viii

relevant safety legislation in the country of use.

AC supply isolation device
The AC supply must be removed from the drive using an approved isolation device or disconnect
before any servicing work is performed, other than adjustments to the settings or parameters
specified in the manual. The drive contains capacitors which remain charged to a potentially lethal
voltage after the supply has been removed. Allow at least 3 minutes after removing the supply
before carrying out any work which may involve contact with electrical connections to the drive.

Products connected by plug and socket
A special hazard may exist where the drive is incorporated into a product which is connected to the
AC supply by a plug and socket. When unplugged, the pins of the plug may be connected to the
drive input, which is only separated from the charge stored in the bus capacitor by semiconductor
devices. To avoid any possibility of electric shock from the pins, if they are accessible, a means
must be provided for automatically disconnecting the plug from the drive (that is, a latching
contactor).

Grounding (Earthing, equipotential bonding)
The drive must be grounded by a conductor sufficient to carry all possible fault current in the event
of a fault. The ground connections shown in the manual must be followed.

Fuses
Fuses or over-current protection must be provided at the input in accordance with the instructions
in the manual.

Isolation of control circuits
The installer must ensure that the external control circuits are isolated from human contact by at
least one layer of insulation rated for use at the applied AC supply voltage.