Super Systems 9200 User Manual
Page 40
Model 9200 Programmable Dual-loop Controller
SSi Manual SERIES 9200
40 Programmable Dual-loop
DEV_AL
This deviation alarm opcode is used to turn the temperature or atmosphere deviation alarms ON
or OFF.
The option values are:
• OFF, turns off both the temperature and atmosphere alarms;
• TEMPERATURE, turns on the temperature alarm and turns off the atmosphere alarm;
• ATMOSPHERE, turns on the atmosphere alarm and turns off the temperature alarm; and
• BOTH, turns on both the temperature and the atmosphere alarms.
• The band limit can be changed by the
SET_WAIT
opcode.
DOW_INQ
This opcode checks the real time clock for the day of the week. This is useful for performing
operations on a weekly basis on a specific day. The option data is the day of the week, i.e. SUN,
MON, TUE, WED, THU, FRI, and SAT.
EVT_IN
This opcode waits for an input event to be turned ON or OFF depending on the option value. The
option value is the event number followed by either ON or OFF.
If temperature data and/or atmosphere data are specified, they are considered set points and will
be sent to the appropriate controller.
EVT_OUT
The event output opcode turns ON or OFF an output event based upon the option value. The
option value is the event number followed by either ON or OFF.
If temperature data and or atmosphere data are specified, they are considered set points and will
be sent to the appropriate controller.
G_Ramp
This is a guaranteed ramp opcode. The temperature and or atmosphere process value must be
within the deviation band to allow the ramp timer to run. The option values are the ramp time in
hours and minutes, temperature and/or atmosphere set point. The band limit can be changed by
the
SET_WAIT
opcode.
G_SOAK
This is a guaranteed soak opcode. The temperature process value must be within the deviation
band to allow the soak timer to run. The option value is the soak time in hours and minutes. The
band limit can be changed by the
SET_WAIT
opcode.
G_SOAK High
This is a guaranteed soak high opcode. The temperature process value must be above the
deviation band to allow the soak timer to run. The option value is the soak time in hours and
minutes. The band limit can be changed by the
SET_WAIT
opcode.
G_SOAK Low
This is a guaranteed soak low opcode. The temperature process value must be below the
deviation band to allow the soak timer to run. The option value is the soak time in hours and
minutes. The band limit can be changed by the
SET_WAIT
opcode.
GOSUB
The go to subroutine opcode is used to call a program and then return to the calling program.
This is used to execute standard routines that can be used by many programs.
GOSUBs
can be
stacked up to eight levels. The option data is the program number.
HIGH_AL
This opcode is used to enable a high limit alarm on the temperature process and/or the
atmosphere process. The temperature data is the high limit point for the temperature process.
The atmosphere data is the high limit point for the atmosphere process. This alarm remains
active until the program ends.
HIGH_PO
This opcode is used to enable a high limit alarm on the temperature percent output and/or the
atmosphere percent output. The temperature data is the high limit point for the temperature