Model 9200 Programmable Dual-loop Controller
SSi Manual SERIES 9200
20 Programmable Dual-loop
cautious not to set the change set point value too low. (E.g. if the furnace controls 1700 in a steady state
at 50% output and you set the change set point value to 40% and the PB value is low, you could find
yourself in a situation where you never see 40% output and remain in a PB only control mode.)
Default PID Parameters for Loop 1(% Carbon) and Loop 2 (Temperature)
Loop 1 Default PID Parameters
Loop 2 Default PID Parameters
Proportional Band: 20
Proportional Band: 4.0
Reset: .10
Reset: 0.10
Rate: 0
Rate: 0
Cycle time: 16
Cycle time: 60
The Cancel key on some of the screens returns you to the previous screen without any changes being
effected. The Esc key takes you back to the Menu Screen.
Event Run Program Setup
Pressing the Enter key takes you to a screen labeled
Event
Run Program (0 to use buffered).
This is used to start a program stored in the 9200, by
contact closure between terminals 21 (Digital In Com) and
17 (Digital In 1). The value entered at program to run will
start with contact closure.
Pressing Enter pops up the Current Value Screen, showing
the current value in the Series 9200. To make an
adjustment, enter the program number, using the numeric
keypad and press the Enter key. This returns you to the
original Event Run Program Screen that now shows the
new program number that you have entered. If you do not
wish to make the change simply press the Esc key which
takes you back to the Event Run Program Screen with NO
change being made to the Event Run Program.
Zone / Load TC Setup
Pressing the Enter key takes you to the following
screen.
This screen is used to set up Load, Monitor
Thermocouples. It is normally used in conjunction
with an ADAM Module to provide information from
the Load Thermocouples. There are three modes of
operation for Load TC Enable. They are Off, On and
On + Alarm. To set the mode on Load TC Enable,
highlight it and press Enter, this will open a new
window, use the blue up and down arrows to
highlight the desired mode then press Enter. This
will enter the selected mode and return you to the
Load TC Screen. By activating a thermocouple, no
conditional soak will start unless the temperature is with the default wait limits of the selected
thermocouple(s).