Super Systems 9200 User Manual
Page 31

Model 9200 Programmable Dual-loop Controller
SSi Manual SERIES 9200
31 Programmable Dual-loop
The current value is displayed directly above the bottom row of buttons as Current CJ value: XX.X ° F.
Pressing the Next -> key displays the following screen.
Pressing the Edit button displays a numeric keypad
allowing you to change the Zero Input 1 range
value. Normally terminals 31 and 32 are shorted for
this step.
After entering the new Zero Input value you must
press Calibrate. Pressing the Calibrate key stores
the appropriate value. Pressing the Done will return
you to the User Calibration Screen.
The current value is displayed directly above the
bottom row of buttons as Current Input 1 value:
XX.X UV.
Pressing the Next -> key displays the following
calibration screen:
Pressing the Edit button displays a numeric keypad
allowing you to change the Span Input 1 range
value. Normally terminals 31(-) and 32(+) have
2000 mV applied for this step.
After entering the new Span Input value you must
press Calibrate. Pressing the Calibrate key stores
the appropriate value. Pressing the Done will return
you to the User Calibration Screen.
The current value is displayed directly above the
bottom row of buttons as Current Input 1 value:
XX.X UV.
Pressing the Next -> key displays the following
calibration screen:
Pressing the Edit button displays a numeric keypad
allowing you to change the Zero Input 2-range
value. Normally terminals 29 and 30 are shorted for
this step.
After entering the new Zero Input value you must
press Calibrate. Pressing the Calibrate key stores
the appropriate value. Pressing the Done will return
you to the User Calibration Screen.
The current value is displayed directly above the
bottom row of buttons as Current Input 2 value: XX.X
UV.
Pressing the Next -> key displays the following
calibration screen: