Error on the probe

An error on a probe only affects the functions that use the probe. The controller can no longer execute the

affected function correctly and stops controlling this function. All other functions of the controller continue to

work properly.

Error on the probe

Terminal

Effect on control

Inlet temperature, primary (TVL)

1,

^

The controller takes 75 °C as the preliminary

value so that regulation can continue to be

carried out.

Hot water temperature, secondary (TWW)

2,

^

The controller uses the temperature value of

the E.1 and T probes for regulation.

Source temperature, primary (TQ)

3,

^

The source temperature has no effect on reg-

ulation.

Cold water temperature, secondary (TKW)

4,

^

The cold water temperature has no effect on

regulation

Hot water temperature, secondary

E.1, T

FriwaMini Basic and Premium: Regulation

stops. FriwaMidi, FriwaMaxi, FriwaMega: The

hot water temperature at terminals 2,

^ is

used for regulation. An error on E.1, T has no

long-term effect on regulation.

Medium flow rate, secondary

E.1, V‘

Regulation stops.

Check the temperature probe Pt1000

DANGER!

Danger of death due to electric shock!
Before opening the unit, ensure that all cables that lead to the unit are disconnected from the mains and

cannot be inadvertently connected to the mains!

1.

Remove the terminal cover.

2.

Disconnect the temperature probe.

3.

Measure the resistance of the temperature probe with an ohmmeter and compare them with the table

below. Slight variations are permitted.

4.

Attach the terminal cover.

Correlation between temperature and resistance

Temperature

[°C]

-30

-20

-10

0

10

20

30

40

50

60

70

Resistance [Ω]

882

922

961

1000

1039

1078

1117

1155

1194

1232

1271

Temperature

[°C]

80

90

100

110

120

130

140

150

160

170

180

Resistance [Ω]

1309

1347

1385

1423

1461

1498

1536

1573

1611

1648

1685

REMKO fresh water station Controller