Current thermal performance: The corresponding

maximum value is displayed when "SET" is

pressed.

Fig. 19: Current thermal performance, maximum

value

Daily heat content: When "SET" is pressed, the

total heat content and the daily heat content are

displayed alternately.

Fig. 20: Display of total heat content and daily heat

content

In cascade operation, each controller displays

its "own" calculated heat content.

Key variable

min. max.

Factory setting

Activation

on, oFF

on

Circulation

Switches a circulation pump that is controlled by

temperature, clock and/or flow on and off. The

three control modes can be combined in any way.

Temperature control: If the temperature on the

circulation return falls below the T

on

value, the cir-

culation pump is switched on until the temperature

reaches the T

off

value. The temperature control is

time-limited if the clock control is activated.

Clock control: If the current time is within one of 3

time windows that can be set, the circulation pump

is:

n

Permanently switched on if the temperature

control is deactivated ("oFF")

n

Controlled by temperature if the temperature

control is activated ("on")

Flow control: Flowing for a short time (<5s)

switches the circulation pump on for the duration of

activation. After the duration of activation expires,

the circulation pump remains switched off at least

for the duration of the waiting time. The flow con-

trol works independent of the clock control.

Key variable

min.

max.

Factory

setting

Activation

on, oFF

oFF

Speed

regulation

0%

100%

40%

Temperature

control (tc)

on, oFF

oFF

Activation

temperature T

on

0 °C

T

off

-2 K

30 °C

Deactivation

temperature T

off

T

on

+2 K

95 °C

35 °C

Clock control

(cc)

on, oFF

oFF

Day

day: 1 to day: 7

-

Time window 1

start/end

0:00

23:59

6:00/8:00

Time window 2

start/end

0:00

23:59

12:00/13:30

Time window 3

start/end

0:00

23:59

18:00/20:00

Flow control

(fc)

on, oFF

oFF

Duration of acti-

vation

1 min

10 min

2 min

Waiting time

0 min

60 min

10 min

Distribution valve in return flow

Switches the distribution valve in the return flow

on. The cold water probe is pre-defined at output

R2.

No further settings are required.

The function can only be activated or deactivated.

R2 on if TKW ≥ 28 °C

R2 off if TKW ≤ 23 °C

REMKO fresh water station Controller

20