7

Commissioning

DANGER!

Danger of death due to electric shock!
Before initial commissioning, carry out all of the

tasks described in

Ä Chapter 5 ‘Assembly and

dismantling’ on page 23 and

Ä Chapter 6

‘Electrical wiring’ on page 25 completely.

After the unit has been disconnected from

the mains for a long time, the date and time

must be set again when switching on (see

steps 1-5 below).

Saved functions that are not connected to

a time setting remain set even after an

extended power failure (> 15 minutes).

The controller is pre-set when it is manufac-

tured. You only have to set the date and time

(Fig. 33).

T

Fig. 33: Setting the time

T: Time

For information about operation, refer to

Values can be changed retroactively within con-

trolled operation. The following applies:

n

"s/ESC/r" navigates forwards and backwards

block by block

(Fig. 33: "s" = forwards; "ESC/r" = backwards).

n

Navigating (with "s/ESC/r") is always pos-

sible after completing a block.

n

Retroactive changes to a block are initiated

using "SET".

You can bring the controller into operation as

follows:

1.

Set up the power supply to the controller.

- The time 12:00 is displayed.

- 12 flashes (Fig. 34)

2.

Press "sr" to set the hour.

3.

Press "SET". The minute flashes.

4.

Press "sr" to set the minutes.

5.

Press "SET".

6.

Repeat steps 4 and 5 to set the year, month

and date.

Fig. 34: Setting the time

REMKO fresh water station Controller

30