Operating mode off

Method of operation

n

All outputs are switched off (outputs/control

outputs switched off, relay open)

DANGER!

The pump lines are still powered because

these are constantly supplied with 230 V

n

"OFF" and the software version are displayed

alternating. Example in Fig. 6: Software version

St 1.3

n

The background lighting is red

n

The variant display can be called (see Fig. 6)

Operation

1.

Press "SET" to call the display of the pre-set

Friwa variant.

Fig. 6: Operating mode off - operation

2.

Press the "r" and " s" buttons at the same

time for 2 seconds, in order to access variant

selection. The pre-set REMKO factory setting

is for the EFS 25 variant 02 and for the EFS

35 variant 04

NOTICE!

The variant may only be changed by a spe-

cialist. Otherwise, we cannot guarantee that

the Controller will function correctly after

changing the variant.

Manual operating mode

Method of operation

n

The background lighting is red, the open-end

wrench symbol

flashes.

n

The outputs of the controller (pumps, valves)

can be switched manually.
Possible switching statuses:
0: Off
1: On
0% ... 100%: Control the HE pump via PWM

(only H1, H2)
A: Automatic operation in accordance with the

settings in the settings menu

n

The current temperatures and operating hours

can be displayed (status display).

n

The Display of the hot water temperature

shows a value that is not smoothed.

n

When switching to manual operation, all out-

puts are set to A, R1 is displayed.

n

Typical use: Function test (maintenance), trou-

bleshooting.

Operation

You can switch the outputs on and off as fol-

lows:

1.

If necessary, press "r s" to select a dif-

ferent output.

2.

Press "SET". The switching status flashes.

3.

Press "r s" to change the switching status.

4.

Press "SET" to apply the change.

Also see (

2

) in the next figure.

13