Remko fresh water station controller – REMKO EFS 25-35 User Manual

Page 32

background image

Error description

Cause

Remedial measures

The controller does not function

The display is blank or dark

The power supply to the controller

is interrupted

n

Check the power supply to the

controller

n

Check the power supply's fuse

The controller continually displays 12:00

"12" flashes

The power supply to the controller

was interrupted for more than 15

minutes

Set the time; saved functions that

are not connected to a time setting

remain set even after an extended

power failure. The circulation (if the

time window "cc" was activated")

and thermal disinfection functions

are inactive

The primary pump does not run even though domestic water is being dispensed

The pump symbol rotates

The power supply or control signal

to the pump is interrupted

Check the mains power and control

line to the pump

The pump is stuck

Unblock the pump, replace it if nec-

essary

The pump symbol does not

rotate

The domestic hot water maximum

temperature is temporarily

exceeded

This is not an error

n

The pump symbol does not

rotate

n

The display is red

n

Flashes

Manual operation is switched on,

output R1 is set to 0 (off)

Switch on automatic operating

mode

n

The pump symbol does not

rotate

n

The display is red

A short circuit or an interruption for

the temperature probe

n

Query the current value of the

connected temperature probe

on the controller

n

Check the probes and cables

The primary pump runs even though no domestic water is being dispensed

The pump symbol rotates

n

The comfort function is active

n

Thermal disinfection is active

n

Circulation is active

n

The probe identifies dispensing

n

The pump runs due to blocking

protection

n

This is not necessarily an error

n

Deactivate the functions if nec-

essary

n

Probe error E.1 (continual dis-

play of a flow)

n

The pump symbol rotates

n

The display is red

n

is displayed

Manual operation is switched on,

output H1 is set to > 10%

Switch on automatic operating

mode

The primary pump is running, domestic water is being dispensed, heat is not transported to the

heat exchanger

The pump symbol rotates

There is air in the primary circuit

Check the primary circuit for air

Shut-off valve closed

Check the shut-off valve

The heat exchanger is dirty or

scaled

Flush/clean the heat exchanger

according to the manufacturer's

instructions.

REMKO fresh water station Controller