Error messages

Errors are displayed as shown below, the background lighting is red. The figures in this section show system

examples.

Display (example) Description

Solution

An interruption was detected on the probe

input displayed (here: probe input 4).

Check the cables and probes connected

to the probe input.

A short circuit was detected on the probe

input displayed (here: probe input 4).

Check the cables and probes connected

to the probe input.

The domestic hot water target tempera-

ture was not reached. Possible causes:

n

The storage tank not heated

n

The shut-off valve in the primary cir-

cuit is closed.

n

There is air in the pipes

n

The primary pump is defective

n

The heat exchanger is scaled

n

Heat up the storage tank

n

Check the shut-off valve

n

Bleed the system

n

Check the pump

n

De-scale the heat exchanger

A short circuit occurred at output R1. Pos-

sible causes:

n

The valve is defective

n

There is a wiring fault

n

Check the valve

n

Check the wiring of R1

Output R1 was overloaded.

Cause: The values permitted for R1

according to the name plate were

exceeded continuously, the output was

switched off.

Check the electrical data of the valve,

replace the valve if necessary. R1 is

switched back on automatically.

A short circuit occurred at output R2.

Possible causes:

n

The valve is defective

n

There is a wiring fault

n

Check the valve

n

Check the wiring of R2

Output R2 was overloaded. Cause: The

values permitted for R1 according to the

name plate were exceeded continuously,

the output was switched off.

Check the electrical data of the valve,

replace the valve if necessary. R2 is

switched back on automatically.