Thermal disinfection

The fresh water station provides higher domestic

hot water temperatures, in order to kill dangerous

germs. At the same time, the circulation pump is

activated, as long as the circulation function was

activated. If the circulation function was not acti-

vated, only the domestic hot water target tempera-

ture in the defined time window is increased to the

disinfection temperature.

Fig. 25: Thermal disinfection

Only one time window per day is available for

thermal disinfection.

Key variable

min.

max.

Factory

setting

Activation

on, oFF

oFF

Disinfection

temperature

60 °C

80 °C

73 °C

Clock control

on, oFF

on

Day

day: 1 to day: 7

-

Time window

0:00

23:59

01:00/02:00

Cascade

Controls cascade operation of two fresh water sta-

tions.

Both controllers are connected to each other via a

communications bus. The connecting line is con-

nected to both controllers at connections 5,

^. If

the minimum cross-section is 0.25 mm

2

, the length

of the bus connection must not exceed 3 m. 2-way

valves must be integrated into the cold water pipe

and connected to R1. The circulation pump must

be plugged into a combined circulation phase pro-

vided by the customer ahead of the two modules.

Use only original REMKO accessories.

Fig. 26: Cascade

The cascade function must be activated in both

controllers; one controller must be configured as

the master (MA) and the other as the slave (SL).

The master controller forwards the following infor-

mation to the slave:

n

"Switch on" command

n

"Switch off" command

n

Domestic hot water target temperature

n

Date and time

Key variable

min. max.

Factory setting

Activation

on, oFF

oFF

Master /

Slave

MA, SL

MA

Alarm output

Controls the set output for the following errors:

n

Probe errors due to a short circuit or an inter-

ruption

n

Medium flow rate errors: Er:1

1)

n

Electronic overload check/fuse has been trig-
gered: Er:2 ... Er:5

1)

1)

more information in

Ä Chapter 8 ‘Trouble-

shooting and customer service’ on page 31

The alarm output is always active

NOTICE!

The signal output R

S

may only be operated

with low voltage up to 24 V and limited power.

REMKO fresh water station Controller