Load Testing:

• Load testing shall only be performed as a bench test.

• While on open circuit, place 100 amp load across each battery for a period of 30 seconds.

• Measure and record end of discharge (E.O.D.) voltage at 30 seconds.

• Calculate average and compare results against value of 10.95

for Type PRC 1250XL E.O.D.@ 30 Seconds and 100 amp load.

• If calculated average E.O.D. of group is observed as being normal, identify and replace

individual batteries with values that are 10% less than the group average.


General Equipment Requirements:

• Digital voltmeter- 3 1/2 digit, minimum 0.25% accuracy.

• Load tester (100 amps) with digital voltage readout, minimum 0.25% accuracy.

• Therometer- thermocouple, contact type, 1

0

C accuracy.

Battery Date Coding:

• The manufacturer stamps the negative terminal post of the battery, with the month and year

date code.


• Shelf life is based on normal storage temperature conditions, 66

0

F ~ 90

0

F and requires

recharging every 6 months from the last full charge date.

WARNING!

• Battery shelf life, when stored under temperature conditions of 66ºF ~ 90ºF is five(5) months

maximum after the ship date.

• Battery must be recharged after this date otherwise they will be damaged.