SECTION 2 – PREINSTALLATION
2-1 Location Considerations
•
Provide an operating environment that meets the following conditions:
Ambient Temperature is 0
O
C to 40
O
C ( 32
O
F to 104
O
F )
Relative Humidity is 10 to 95 % Non-Condensing.
2-2 Positioning
•
Allow at least a minimum of 3 inches to the rear for airflow. The PBC is air cool by convection.
•
Door shall have full 110 degrees open clearance, and have 5 feet clearance in front for basket or platform.
DANGER
•
Inspection Safety Zone of Tray is 6 inches. Pass that point the tray needs support, due to weight.
•
The Electronic Tray weight varies by model and is approximately 52 to 57 lbs.
•
The Battery Tray weight varies by model and is approximately 200 to 290 lbs.
•
The PBC varies by model and is approximately 365 to 455 lbs.
2-3 Mechanical Overall Dimensions and Weight
Model
Rating
Maximum Cabinet Dimensions
Maximum
Weight
Lifting Hole
Diameter
650 W
19.5” W x 20” H x 20.75” D
365 lbs.
0.875
650 W
# 1 20.25” W x 26” H x 20.75” D
375 lbs.
0.875
LU0.4xxx
&
LU0.7xxx
650 W
# 2 20.25” W x 27.5” H x 20.75” D
385 lbs.
0.875
1300 W
19.5” W x 20” H x 20.75” D
455 lbs.
0.875
1300 W
# 1 20.25” W x 26” H x 20.75” D
465 lbs.
0.875
LU1.5XXX
1300 W
# 2 20.25” W x 27.5” H x 20.75” D
475 lbs.
0.875
Note: # 1 PBC Height with Lifting & Pole Mounting Plates.
# 2 PBC Height with Pad mounting Plates and Lifting Plates.
NOTE: 1300W models IS de-rated to 400W UPS when used in; Sealed cabinet for environmental protection
application, units have no louvers or when a sealing kit option is add to a louver unit.
NO! Change in the weight of sealed cabinets units. Add 10 pounds to weight for Sealing Kit.
2-4 Site Planning Specifications
Nominal
Input
Voltage
220 VAC
230 VAC
120 VAC
220 VAC
240 VAC
Input Voltage
Range
168 -- 264
168 -- 264
85 -- 132
168 -- 264
168 -- 264
Max. Input
Voltage
264 VAC
264 VAC
132 VAC
264 VAC
264 VAC
Input Frequency
*
50 Hz
50 Hz
60 Hz
60 Hz
60 Hz
Output
Frequency
50 Hz
± 0.5 %
50 Hz
± 0.5 %
60 Hz
± 0.5 %
60 Hz
± 0.5 %
60 Hz
± 0.5 %
Output Voltage
230 VAC
±3%
230 VAC
±3%
120 VAC
± 3%
240 VAC
±3%
240VAC
± 3%
* Factory pre-set. Can be selected for either 50 or 60 Hz.
2-5 Site Detail Electrical Specifications
• See page 7, Section 1-8 and 1-9 for more details.
14