beautypg.com

Appendix c – OnLine Power PBC I User Manual

Page 41

background image

Appendix C:

Battery Maintenance Testing & Specifications

Battery Specifications:

• Battery Impedance - The battery impedance value is measured @ 25

o C

. This value is for new

batteries at full state of charge, on open circuit at a frequency of 30 Hz. Battery type PRC-1250XL
impedance is 5.05 milliohms.

• Float Voltage - The specified float voltage “ window ” is 2.27 - 2.30 V.P.C. @ 25

0

C. This value

will help in reducing recharge times and keeping the batteries at the highest state of charge.

Recommended Procedures:

These methods are designed to be used on a battery system installed for a minimum period of 6
month, in a steady state of float condition and not under conditions of high current recharge or
discharge.

Measure Float Voltage:

• When the low battery LED is “ ON ” over 24 hours test system, remove the battery tray plug

from the battery jack on the electronic tray, so readings can be taken.

• Measure and record system voltage directly across the battery plug.

• If the battery system is determined to be low voltage system after 24 hours of charging the

system voltage will be only 3% low, remove and replace the battery tray.


Battery Servicing:

• Measure and record a 10% sample of individual battery temperatures at the negative terminal

post.


• Identify batteries that are greater than 3

o

C above ambient from the calculated average. If no

external causes for higher battery temperatures are noted.


• Check that the filters are clean and Fans are operational.

• If no change is noted, remove and replace the battery tray.


Visual Inspections:

• Examine batteries for any abnormalities in end wall bulge, post leakage, cover to cells

leakage, etc.

• Identify any end wall bulges that exceed 1/2 inch compared to the other batteries in tray.








34