Model numbers and specifications – OnLine Power PBC I User Manual
Page 20

MODEL NUMBERS AND SPECIFICATIONS
INPUT SPECIFICATIONS
OUTPUT SPECIFICATIONS
Nominal Input Voltage: 120, 220, 240 or
Output Voltage: Same voltage as Input or multiple
277 VAC single phase.
output 120/240, 120/208 or 120/277 VAC.
Input Voltage Range: -20% to +15%.
Voltage Regulation: ±3%(HE), ±0.5% (LU).
Input Frequency: 60 or 50 Hz, ±5%.
Frequency: 60 Hz ±0.5 Hz, or 50Hz ±5%.
Overcurrent Protection: Circuit breakers.
Harmonic Distortion: <5% THD; <3% single harmonic.
Power Connection: Hard Wired (TB).
Crest Factor: 3 to 1.
Input Configuration: 2 wire plus ground.
Power Factor: 0.7 leading load to 1.0 P.F.
Noise Rejection: -120 dB common mode;
ENVIRONMENT
-60 dB normal mode.
Battery Back-up Times: Range from 2 min. to 13 hrs.
Operating Temperature: -40° to +58°C.
Consult factory for longer backup time.
Storage & Transport Temp: -40°C to +60°C.
Operating Relative Humidity: 0 to 100%.
PHYSICAL SPECIFICATIONS
Solar Loading: Q = 70 W/ft
Mounting: Pad Mount, Pole Mount Provision.
2
s
Operating Altitude: -1000 to +13,000 feet,
Accessibility: All servicing is through the front:
referenced to sea level. Temperature
no side or back require and cable entry from
Compensated Battery Charger.
bottom or side (Nema 3R or 4X Cabinets).
NEMA 3R Cabinet:
Model No.
Max.
Watts
**Backup time
Range
***(Qty.) Battery
Cabinet
Size
Inverter wgt
W/O Battery
100
30 min – 4hrs
150 LB
200
30 min – 2hrs
150 LB
LU0.4XXX
400
30 min – 3hrs
(4) 12V
48 VDC
165 LB
500
30 min – 3hrs
220 LB
600
30 min – 2hrs
240 LB
700
30 min – 2hrs
240 LB
1000
15 – 60 min
260 LB
1300
15 – 60 min
260 LB
LU0.5XXX
1400
15 – 30 min
(6) 12V
72 VDC
19.5" Wide
23" High
21" Deep
260 LB
NEMA 4 Cabinet:
Model No.
Max.
Watts
**Backup time
Range
***(Qty.) Battery
Cabinet
Size
Inverter wgt
W/O Battery
100
30 min – 6hrs
200 LB
200
30 min – 6hrs
200 LB
400
30 min – 4hrs
220 LB
500
30 min – 3hrs
240 LB
600
30 min – 2hrs
240 LB
LU0.7XXX
700
30 min – 2hrs
(6) 12V
72 VDC
19.5" Wide
23" High
21" Deep
240 LB
*
Battery tray weight varies by model and is proximally 200 to 290 LBS and installed in the same
cabinet. For other backup times; consult factory.