Sc-1608-2ao-enet, Compatible modules, Ssr digital i/o control modules – Measurement Computing SC-1608 Series User Manual
Page 9
![background image](https://www.manualsdir.com/files/797518/content/doc009.png)
SC-1608 Series User's Guide
Introducing the SC-1608 Series
9
SC-1608-2AO-ENET
Figure 3 shows the functionality provided by a SC-1608-2AO-ENET with analog I/O 8B modules and digital
I/O SSR modules installed.
Figure 3. SC-1608-2AO-ENET functionality
The E-1608-OEM receives power from the included external supply when the baseboard is powered on. When
connected to the baseboard, the E-1608-OEM power header connector (
W1
on the OEM DAQ board) mates
with the +5 V power header connector (
J37
) on the baseboard. No additional supply is required.
Compatible modules
When using the SC-1608X-2AO-USB, SC-1608X-USB, SC-1608-USB, the total current available for 8B
analog I/O modules and SSR digital I/O modules is 1612 mA, maximum. When using the SC-1608-2AO-
ENET, the total current available for 8B analog I/O modules and SSR digital I/O modules is 1292 mA,
maximum. Keep these values in mind when installing modules.
SSR digital I/O control modules
SSR digital I/O modules are solid state relay control modules that provide 4000 Vrms optical isolation. Digital
input modules sense AC/DC voltages from field devices and convert them to digital TTL signals. Digital output
modules use TTL signals to switch and control AC/DC loads.
The baseboard has eight locations for single channel solid state relay modules. The input/output type is
configured with onboard switch
SW2
. The polarity is configured with onboard jumper
W1
. The table below lists
the input and output modules that you can install.
SSR digital I/O modules compatible with the SC-1608 Series
SSR module type
Description
AC sense, 90 to 140 VAC/VDC
AC sense, 180 to 280 VAC/VDC
DC sense, 3 to 32 VDC