MDE-4096C Blackmer® Global Dispenser Pump Operation, Maintenance and Kit Installation Manual · April 2008

Maintenance

OIML Switch Removal

To remove OIML switch, proceed as follows:

1

Cut and remove tamper resist wire.

2

Using a wrench, rotate the OIML Switch assembly (22) in a counterclockwise (CCW)
direction and remove it (see

Figure 9

on

page 21

).

Do not allow debris to fall into open port.

CAUTION

OIML Switch Installation

To install the OIML switch, proceed as follows:

1

Apply a very thin film of thread sealing compound onto the thread, beginning at about 3 mm
from the end.

Thread sealing tape is not advised as it may cause contamination.

CAUTION

2

Rotate the OIML switch assembly (22) threads in a clockwise (CW) direction into the sump
vent port by hand and tighten firmly with wrench (see

Figure 9

on

page 21

).

Do not allow debris to fall into open port.

CAUTION

3

Secure new tamper resist wire through appropriate holes in the switch body and pump casing
tab.