Model 9820k – Gasboy 9120K Series Installation User Manual
Page 6

Introduction
General Description
Page 2
MDE-4567C 9120K and 9820K Series AST Pumps Installation and Operation Manual · September 2008
Model 9820K
The Gasboy Series 9820K Aboveground Storage Tank Remote Access (ASTRA) pump units
are UL-listed.
Note: NFPA regulations do not allow tank-mounted pumps to be used for the resale of fuel.
The 9820K Series units consist of two metal cabinet assemblies.
• One assembly is mounted on top of the tank and contains the pumping unit, meter,
electronic pulser, and all hydraulics. The hose and nozzle are connected to this assembly.
• The second assembly is mounted at a height to permit easy access by a user. It contains the
electronic register, controls, display and nozzle boot.
The standard features and specifications of the 9820K Series pumps are as follows:
• One-inch high, 6-digit, backlighted Liquid Crystal Display (LCD)
• 1000:1 dual-phase, error-checking pulser (gallons); 250:1 dual-phase, error-checking
pulser (liters)
• AC authorization line for control of the unit
• Reset complete (Switch Detect) output that allows monitoring of the unit's operation when
it is connected to an automated fueling system
• Resettable electronic totalizer
• Discharge elbow
• Both models use a quiet and efficient pump which features an air eliminator built into the
pump casting. The pump meter is a three-piston, positive displacement meter which is
tested and calibrated for accuracy at any speed or pressure up to the maximum working
pressure of 50 psi.
• The standard pumping cabinet finish is white. The electronic register cabinet is black with
a blue graphics panel.
• Dual Stage Solenoid Valve
• Filter
The available options and accessories for the Gasboy Series 9820K pumps are as follows:
• Pulser output drive line (open collector), capable of driving 1, 10, 100, 250 and 500 pulses
per unit (gallons) or 1, 10, and 100 pulses per unit (liters)
• RS-485 communication for direct connect to Gasboy CFN equipment
• Battery backup for display of last transaction and capture of stored pulse count in the event
of a power failure.
• Mechanical totalizer
• A working voltage of 115 VAC (115/230 for motor) 60 Hz for domestic use, 230 VAC 50
Hz/60 Hz for international use.
• Other options include Listed automatic nozzles, special lengths of Listed hose assembly,
Listed dual swivels, UL-recognized filters, Vapor Recovery, and Vapor Recovery Ready.