MDE-4567C 9120K and 9820K Series AST Pumps Installation and Operation Manual · September 2008

Page 27

Installation Precautions

Installation

5 – Installation

Installation Precautions

All installations must conform with all building/fire codes, all Federal, State, and Local codes,
National Electrical Code, NFPA 70, NFPA 30, and Automotive and Marine Service Station
Code (NFPA 30A) codes and regulations. Canadian users must also comply with the Canadian
Electrical Code.

Plan your installation carefully. A pump cannot be expected to work satisfactorily unless the
installation is correct. Pumping troubles, which seem to be pump-related, are frequently traced
to faulty installation. Review the following list of installation DOs and DO NOTs to avoid
potential problems.

Installation DOs

DO read the

“Important Safety Information”

on

page 5

. It contains important information

regarding the safe use of your pumping equipment.

DO install an emergency power cutoff. In addition to circuit breaker requirements of

NFPA 70 and NFPA 30A, a single control which simultaneously removes AC power from
all site pumping equipment is recommended. This control must be readily accessible,
clearly labeled, and in accordance with all local codes.

The DISABLE PUMPS, and STOP buttons at the facility building and the optional
DISABLE PUMPS button on the Island Card Reader (ICR) WILL NOT shut off
electrical power to the pump.

This means that even if you activate these stops, fuel may continue to flow
uncontrolled.

You must use the TOTAL ELECTRICAL SHUT-OFF in case of an emergency and
not only these facility building and ICR station “stops”.

WARNING

!