MDE-4567C 9120K and 9820K Series AST Pumps Installation and Operation Manual · September 2008

Page 17

Wiring Diagrams

Wiring

Wiring Notes for Model 9120K (

Figure 3-2

on

page 16

)

Notes:1) All wiring and conduit runs must conform with all building/fire codes, all Federal,

State, and Local codes, the National Electrical Code, (NFPA 70), NFPA 30, and
Automotive and Marine Service Station Code (NFPA 30A) codes and regulations.
Canadian users must also comply with the Canadian Electrical Code.

2) Pump Motors may be wired as 230 VAC to reduce current draw.

3) The brown wire (Aux AC Control Lead) is shipped capped from the factory. When

used, it connects to a solenoid valve or fuel management system. Do not connect this
wire without first checking the ON voltage of this line to ascertain compatibility with
the equipment being connected.

4) Use the wire size chart in

“Wire Size”

on

page 11

to determine the wire size for

control wiring.

5) Pulser wiring must be installed in metal conduit separate from all AC wiring.