beautypg.com

Errors during slave start-up, Error code 7, Error code 8 – BECKHOFF BK3xx0 User Manual

Page 71: Error code 9

background image

Notes on the Documentation

Fieldbus Components

69

Error code 7

Error code 7 indicates a variety of errors when checking the CfgData. The error argument describes the error.

Error argument

Description

1

The length of the CfgData received is not correct

2

The syntax of the CfgData received is not correct

3

The length of the DP input data that has been calculated from the CfgData is too large

4

The length of the DP output data that has been calculated from the CfgData is too large

Errors during slave start-up

Error code 8

Error code 8 indicates that the length of the DP buffer is greater than the size of the DP RAM in the PROFIBUS
ASIC. The error argument contains the difference (divided by 8). DP communication is deactivated.

Error code 9

Error code 9 indicates a variety of errors that may be detected as the device boots. The error argument describes the
error.

Error argument

Description

1

The length of the DP input data is too great (too many modules are inserted)

2

The length of the DP output data is too great (too many modules are inserted)

3

The length of the CfgData is too great (too many modules are inserted)