K-bus leds (local errors) – BECKHOFF BK3xx0 User Manual
Page 65
Notes on the Documentation
Fieldbus Components
63
K-Bus LEDs (local errors)
Two LEDs, the K-Bus LEDs, indicate the operational state of the Bus Terminals and the connection to these Bus
Terminals. The green LED (I/O RUN) lights up in order to indicate fault-free operation. The red LED (I/O ERR) flashes
with two different frequencies in order to indicate an error. The errors are displayed in the blink code in the following
way:
Error type
Error code
Error code
argument
Description
Remedy
Persistent,
continuous
blinking
-
General K-bus error.
Check the Bus Terminal strip
0
EEPROM checksum
error.
Set manufacturer’s setting with the KS2000
software
1
Inline code buffer
overflow.
Connect fewer Bus Terminals; too many entries
in the table for the programmed configuration
1 pulse
2
Unknown data type.
Software update required for the coupler
0
Programmed
configuration incorrect.
Check programmed configuration for correctness
2 pulses
n>0
Incorrect table entry Bus
Coupler / incorrect table
comparison (Bus Terminal
n).
Correct table entry / Bus Coupler
No Bus Terminal connected; attach Bus
Terminals
3 pulses
0
K-Bus command error.
One of the Bus Terminals is defective; halve the
number of Bus Terminals attached and check
whether the error is still present with the
remaining Bus Terminals. Repeat until the
defective Bus Terminal is located.
4 pulses
0
n
K-Bus data error, break
behind Bus Terminal n.
Check whether the n+1 Bus Terminal is correctly
connected; replace if necessary.
Check whether the End Terminal 9010 is
connected.
5 pulses
n
K-Bus error in register
communication with Bus
Terminal n.
Replace Bus Terminal n.
7 pulses
n
BK3x10 or LC3100:
unsupported Bus
Terminal detected at
location n.
Only use digital (bit oriented) Bus Terminals, or
use a BK3120 Bus Coupler.
9 pulses
0
Checksum error in
program flash memory.
Set manufacturer's setting with the KS2000.
13 pulses
0
Runtime K-Bus command
error.
One of the Bus Terminals is defective; halve the
number of Bus Terminals attached and check
whether the error is still present with the
remaining Bus Terminals. Repeat until the
defective Bus Terminal is located.
14 pulses
n
Bus Terminal n has the
wrong format
Start the coupler again, and if the error occurs
again then exchange the Bus Terminal.