beautypg.com

K-bus leds (local errors) – BECKHOFF BK3xx0 User Manual

Page 65

background image

Notes on the Documentation

Fieldbus Components

63

K-Bus LEDs (local errors)

Two LEDs, the K-Bus LEDs, indicate the operational state of the Bus Terminals and the connection to these Bus
Terminals. The green LED (I/O RUN) lights up in order to indicate fault-free operation. The red LED (I/O ERR) flashes
with two different frequencies in order to indicate an error. The errors are displayed in the blink code in the following
way:

Error type

Error code

Error code
argument

Description

Remedy

Persistent,
continuous
blinking

-

General K-bus error.

Check the Bus Terminal strip

0

EEPROM checksum
error.

Set manufacturer’s setting with the KS2000
software

1

Inline code buffer
overflow.

Connect fewer Bus Terminals; too many entries
in the table for the programmed configuration

1 pulse

2

Unknown data type.

Software update required for the coupler

0

Programmed
configuration incorrect.

Check programmed configuration for correctness

2 pulses

n>0

Incorrect table entry Bus
Coupler / incorrect table
comparison (Bus Terminal
n).

Correct table entry / Bus Coupler

No Bus Terminal connected; attach Bus
Terminals

3 pulses

0

K-Bus command error.

One of the Bus Terminals is defective; halve the
number of Bus Terminals attached and check
whether the error is still present with the
remaining Bus Terminals. Repeat until the
defective Bus Terminal is located.

4 pulses

0
n

K-Bus data error, break
behind Bus Terminal n.

Check whether the n+1 Bus Terminal is correctly
connected; replace if necessary.
Check whether the End Terminal 9010 is
connected.

5 pulses

n

K-Bus error in register
communication with Bus
Terminal n.

Replace Bus Terminal n.

7 pulses

n

BK3x10 or LC3100:
unsupported Bus
Terminal detected at
location n.

Only use digital (bit oriented) Bus Terminals, or
use a BK3120 Bus Coupler.

9 pulses

0

Checksum error in
program flash memory.

Set manufacturer's setting with the KS2000.

13 pulses

0

Runtime K-Bus command
error.

One of the Bus Terminals is defective; halve the
number of Bus Terminals attached and check
whether the error is still present with the
remaining Bus Terminals. Repeat until the
defective Bus Terminal is located.

14 pulses

n

Bus Terminal n has the
wrong format

Start the coupler again, and if the error occurs
again then exchange the Bus Terminal.