beautypg.com

BECKHOFF BK3xx0 User Manual

Page 69

background image

Notes on the Documentation

Fieldbus Components

67

Errors in the modules (terminals, IP modules, IE module, etc.)

Diagnosis of the modules must be activated through the UserPrmData.

Couplers with a maximum of 64 possible modules

Byte Bit Description

16

0-
5

Module number (0-63) with an error (bit 6 of the status bytes is set, except for the serial interface
modules (KL6001, KL6011, KL6021, IP6002, IP6012, IP6022, IE6002, IE6012, IE6022), where bit
3 of the status byte is set)

16

6-
7

Associated channel number (0-3)`

17

0-
7

Status byte of the faulty channel (bits 0-7)

18

0-
5

Module number (0-63) with an error (bit 6 of the status bytes is set, except for the serial interface
modules (KL6001, KL6011, KL6021, IP6002, IP6012, IP6022, IE6002, IE6012, IE6022), where bit
3 of the status byte is set)

18

6-
7

Associated channel number (0-3)`

19

0-
7

Status byte of the faulty channel (bits 0-7)

...

...

...

60

0-
5

Module number (0-63) with an error (bit 6 of the status bytes is set, except for the serial interface
modules (KL6001, KL6011, KL6021, IP6002, IP6012, IP6022, IE6002, IE6012, IE6022), where bit
3 of the status byte is set)

60

6-
7

Associated channel number (0-3)`

61

0-
7

Status byte of the faulty channel (bits 0-7)

Couplers with a maximum of more than 64 possible modules

Byte Bit Description

16

0-
7

Module number (1-255) with an error (bit 6 of the status bytes is set, except for the serial interface
modules (KL6001, KL6011, KL6021, IP6002, IP6012, IP6022, IE6002, IE6012, IE6022), where bit
3 of the status byte is set)

17

6-
7

Associated channel number (0-3)`

17

0-
5

Status byte of the faulty channel (bits 0-5)

18

0-
7

Module number (1-255) with an error (bit 6 of the status bytes is set, except for the serial interface
modules (KL6001, KL6011, KL6021, IP6002, IP6012, IP6022, IE6002, IE6012, IE6022), where bit
3 of the status byte is set)

19

6-
7

Associated channel number (0-3)`

19

0-
5

Status byte of the faulty channel (bits 0-5)

...

...

...

60

0-
7

Module number (1-255) with an error (bit 6 of the status bytes is set, except for the serial interface
modules (KL6001, KL6011, KL6021, IP6002, IP6012, IP6022, IE6002, IE6012, IE6022), where bit
3 of the status byte is set)

61

6-
7

Associated channel number (0-3)`

61

0-
5