Lc3100, Dia-led blink codes – BECKHOFF BK3xx0 User Manual
Page 64
Notes on the Documentation
62
Fieldbus Components
LC3100
I/O-
RUN
BF
RUN Meaning
Remedy
on
off
on
Operating state: RUN, Inputs are read
and outputs are set
Everything is operating correctly
on
on,
blinking
on
1. Bus activity, but slave is already
parameterised
Start master
2. Bus error with reaction to
PROFIBUS error:
a.) K-Bus outputs become 0 or b.) K-
Bus outputs are retained
Check parameters, configuration
(possible error in DP start-up)
off
off
on
Data exchange with the master is not
started
Starts the PLC
off
on
off
No bus activity
Start the master, check the bus cable
off
on,
blinking
on
Bus error with reaction to PROFIBUS
error: K-Bus cycle is stopped
Start master, check parameters,
configuration (possible error in DP start-
up)
DIA-LED blink codes
If an error occurs in the parameterisation or configuration during DP start-up, this is indicated both through the
fieldbus LEDs and in the diagnostic data.
Blink Code
Fast blinking
Start of the error code
First slow sequence
Error code
Second slow sequence
Error argument (error location)