beautypg.com

Lc3100, Dia-led blink codes – BECKHOFF BK3xx0 User Manual

Page 64

background image

Notes on the Documentation

62

Fieldbus Components

LC3100

I/O-
RUN

BF

RUN Meaning

Remedy

on

off

on

Operating state: RUN, Inputs are read
and outputs are set

Everything is operating correctly

on

on,
blinking

on

1. Bus activity, but slave is already
parameterised

Start master

2. Bus error with reaction to
PROFIBUS error:
a.) K-Bus outputs become 0 or b.) K-
Bus outputs are retained

Check parameters, configuration
(possible error in DP start-up)

off

off

on

Data exchange with the master is not
started

Starts the PLC

off

on

off

No bus activity

Start the master, check the bus cable

off

on,
blinking

on

Bus error with reaction to PROFIBUS
error: K-Bus cycle is stopped

Start master, check parameters,
configuration (possible error in DP start-
up)

DIA-LED blink codes

If an error occurs in the parameterisation or configuration during DP start-up, this is indicated both through the
fieldbus LEDs and in the diagnostic data.

Blink Code

Fast blinking

Start of the error code

First slow sequence

Error code

Second slow sequence

Error argument (error location)