beautypg.com

BECKHOFF BK3xx0 User Manual

Page 66

background image

Notes on the Documentation

64

Fieldbus Components

Error
code

Error code
argument

Description

Remedy

15 pulses

n

Number of Bus Terminals is no
longer correct

16 pulses

n

Length of the K-Bus data (bit
length) is no longer correct. n =
bit length after booting

17 pulses

n

Number of Bus Terminals is no
longer correct.
n = number of Bus Terminals
after booting.

18 pulses

n

Bus Terminal identifier no longer
correct after reset (n = Bus
Terminal number).

Start the coupler again, and if the error occurs
again after this, use the KS2000 software to
set manufacturer’s settings.

Error location
The number of pulses indicates the position of the last Bus Terminal before the fault. Passive Bus Terminals, such as
a power feed terminal, are not included in the count.