BECKHOFF BK3xx0 User Manual
Page 10

Notes on the Documentation
8
Fieldbus Components
Technical data BK3150
Type
BK3150
Number of Bus Terminals
64 (255 with K-Bus extension)
Digital peripheral signals
max. 1020 inputs/outputs
Analog peripheral signals
max. 64 inputs/outputs
Configuration possibility
Via the KS2000 configuration software or the controller
Maximum number of bytes
(inputs and outputs)
128 Byte (DP operation only)
Baud rate (automatic detection)
up to max. 12 MBaud
Bus connection
1 x D-sub plug, 9-pin with shielding
Power supply (Us)
24 V
DC
(-15 % /+20 %) To meet the UL requirements use a 4 A fuse or
a power supply that has to satisfy NEC class 2!
Input current (Us)
70 mA + (total K bus current)/4, max. 320 mA
Starting current (Us)
2,5 x continuous current
Recommended fuse
maximum 10 A
K-Bus power supply up to
1000 mA
Power contact voltage
maximum 24 V
DC
Power contact current load
maximum 10 A
Electrical isolation
power contact / supply / fieldbus
Dielectric strength
500 V
rms
(power contact / supply / fieldbus)
Weight
app. 100 g
Permissible ambient temperature
(operation)
0 °C … +55 °C
Permissible ambient temperature
(storage)
-25 °C … +85 °C
Permissible relative humidity
95 % (no condensation)
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC resistance Burst / ESD
according to EN 61000-6-2 / EN 61000-6-4
Protection class
IP 20
Installation position
variable