Notes on the Documentation

Fieldbus Components

61

BK3xx0

I/O-
RUN

BF DIA

Meaning

Remedy

on

off off

Operating state: RUN, Inputs are read
and outputs are set

Everything is operating correctly

on

on off,

blinking

1. Bus activity, but slave is already
parameterised

Start master

2. Bus error with reaction to
PROFIBUS error:
a.) K-Bus outputs become 0 or b.) K-
Bus outputs are retained

Check parameters, configuration (possible
error in DP start-up)

off

off off

Data exchange with the master is not
started

Starts the PLC

off

on on

No bus activity

Start the master, check the bus cable

off

on off,

blinking

Bus error with reaction to PROFIBUS
error: K-Bus cycle is stopped

Start master, check parameters,
configuration (possible error in DP start-
up)