The Bus Coupler's UserPrmData

The following settings can be made in the Bus Coupler's UserPrmData. So that a more easily understood GSD file is
obtained in 90% of applications, some of the settings are only contained in text form in the extended GSD file, and
these are indicated in the last column by Extended. The standard settings are contained both in the standard and the
extended GSD file.

Byte Bit Value Description

GSD file

0

bin

MSAC_C1 connection is not active (default)

0

7

1

bin

MSAC_C1 connection is active (see DPV1)

Standard

0

bin

CfgData checking is active (default)

1

0

1

bin

CfgData checking deactivated (see Deactivating the CfgData checking)

Extended

0

bin

Diagnostic data is transferred in a form compatible with the BK3100

2

3

1

bin

Diagnostic data is transferred in a form compatible with DPV1 (default)

Extended

0

bin

Multi-configuration mode is not active (default)

3

3

1

bin

Multi-configuration mode is active (see Multi-configuration mode)

Extended

0

bin

K-Bus cycle counter is not active (default)

3

4

1

bin

K-Bus cycle counter is active (see K-Bus cycle)

Extended

0

bin

Dummy output byte not active (default)

3

5

1

bin

Dummy output byte is active (see K-Bus cycle)

Extended

0

bin

In multi-configuration mode, the coupler sets the Stat_Diag bit in the
diagnostic data if the configuration is not consistent, and does not yet enter
data exchange (default).

3

6

1

bin

In multi-configuration mode the coupler also enters data exchange even when
the configuration is not consistent, although K-Bus cycles are not yet
executed (see Multi-configuration mode)

Extended

0

bin

2-byte PLC interface not activated (default)

5

0

1

bin

2-byte PLC interface is active (see 2-byte PLC interface)

Extended

0

bin

Response to K-Bus error: manual K-Bus reset (default) (see K-Bus
interruption)

7

0

1

bin

Response to K-Bus error: automatic K-Bus reset

Standard

0

bin

Terminal diagnosis is not active (default) (see Terminal diagnosis)

7

1

1

bin

Terminal diagnosis is active

Standard

0

bin

Diagnostic data for digital terminals included in process image (default) (see
Terminal diagnosis)

7

4

1

bin

Diagnostic data of digital terminals not in the process image (default)

Standard

0

bin

Analog modules are mapped in compact form (only showing the input and/or
output user data) (this is the default, only relevant when CfgData checking
has been deactivated, otherwise the terminals are set by means of the
CfgData) (see Deactivation of CfgData checking)

9

2

1

bin

Analog modules are mapped in complex form (with control/status for register
access and with the same data length in inputs and outputs) (only relevant
when CfgData checking has been deactivated, otherwise the terminals are set
by means of the CfgData)

Extended

0

bin

Representation in INTEL format

9

3

1

bin

Representation in Motorola format (default)

Standard

0

bin

K-Bus mode slow FreeRun (default) (see K-Bus cycle)

9

4

1

bin

K-Bus mode fast FreeRun

Standard