CHASSIS

GND

TB3

TB1B

TB1A

CHASSIS

GND

Figure 3-2: Location of AC Input Connection Block (TB3) and Chassis Ground Connection

Note: To comply with product safety requirements, EARTH GROUND must be

connected to the chassis of the AC power system using the ground stud located
directly below the AC input fuse block. Use a Green/Yellow ground wire.

Note: DO NOT USE THE NEUTRAL CONNECTION OF A 3 PHASE Y AC POWER

CONNECTION IN PLACE OF A TRUE EARTH GROUND CONNECTION. AC power
system neutrals cannot be used for protective earth ground.

The mains source must have a current rating equal to or greater than the input fuses and the
input wiring must be sized to satisfy the applicable electrical codes. All covers must be re-
installed prior to use and the strain relief provisions located at the rear bottom of the unit must be
used to maintain protection against hazardous conditions.

AC Line input
fuses location