AMETEK Programmable Power

RS Series

12

2. Specifications

Specifications shown are valid over an ambient temperature range of 25

±

5

°

C and apply after a

30 minute warm-up time. Unless otherwise noted, all specifications are per phase for sine wave
output into a resistive load. For three phase configurations or mode of operation, all
specifications are for Line to Neutral (L-N) and phase angle specifications are valid under
balanced load conditions only.

2.1 Electrical

2.1.1 Input

Parameter

RS90

RS180

RS270

RS360

RS450

RS540

Line Voltage:
(3 phase, 3
wire + ground
(PE))

208 V

LL

±

10%

230 V

LL

±

10%

400 V

LL

±

10%

480 V

LL

±

10%

Line VA:

106 KVA

212 KVA

318 KVA

424 KVA

530 KVA

636 KVA

Line Current:

350 A

RMS

@

187 V

LL

314 A

RMS

@

207 V

LL

180 A

RMS

@

360 V

LL

150 A

RMS

@

432 V

LL

Each RS90

chassis

requires its

own AC

service.

Total Line

currents are

2 x RS90

Each RS90

chassis

requires its

own AC
service.

Total Line

currents are

3 x RS90

Each RS90

chassis

requires its

own AC

service.

Total Line

currents are

4 x RS90

Each RS90

chassis

requires its

own AC

service.

Total Line

currents are

5 x RS90

Each RS90

chassis

requires its

own AC
service.

Total Line

currents are

6 x RS90

Line
Frequency:

47-63 Hz

Efficiency:

85 % (typical) depending on line and load

Power Factor:

0.95 (typical) / 0.99 at full power.

Inrush Current:

460

A

pk

@

208 V

LL

440A

pk

@

230

V

LL

264A

pk

@

400

V

LL

220A

pk

@

480

V

LL

Each RS90

chassis

requires its

own AC

service.

Total Peak

currents are

2 x RS90

Each RS90

chassis

requires its

own AC
service.

Total Peak

currents are

3 x RS90

Each RS90

chassis

requires its

own AC

service.

Total Peak

currents are

4 x RS90

Each RS90

chassis

requires its

own AC

service.

Total Peak

currents are

5 x RS90

Each RS90

chassis

requires its

own AC
service.

Total Peak

currents are

6 x RS90

Hold-Up Time:

> 10 ms

Isolation
Voltage:

2200 VAC input to output

1350 VAC input to chassis