AMETEK RS Series User Manual

Page 17

background image

User Manual

AMETEK Programmable Power

RS Series

17






















2.1.3 AC Measurements

Measurement specifications apply to RS90 model only. See notes for other models and
configurations.

Parameter

Range

Accuracy (

±

)

Resolution

Frequency

16.00 - 820.0 Hz

0.01% + 0.01 Hz
±0.25 % for the FC option

0.01 to 81.91 Hz
0.1 to 500 Hz
1 Hz above 500 Hz

RMS Voltage

0 - 300 Volts

0.1% FS, < 100 Hz
0.2% FS, > 100 Hz

0.01 Volt

RMS Current

0 - 250 Amps

0.5% FS, < 100 Hz
1.0% FS, > 100 Hz

0.1 Amp

Peak Current

0 - 750 Amps

2% FS, < 100 Hz
4% FS, > 100 Hz

0.1 Amp

VA Power

0 - 30 KVA

1% FS , < 100 Hz
2% FS, > 100 Hz

10 VA

Real Power

0 - 30 KW

1% FS, < 100 Hz
2% FS, > 100 Hz

10 W

Power Factor
(>0.2kVA)

0.00 - 1.00

0.01, <100 Hz
0.02, 100-820 Hz

0.01

Note: Accuracy specifications are valid above 100 counts. For current and power measurements,
specifications apply from 2% to 100% of measurement range.

Note: Power factor accuracy applies for PF > 0.5 and VA > 50 % of max.

Figure 2-4: Voltage / Current Rating Chart for 200/400 V DC Ranges – Derated