beautypg.com

2 mechanical – AMETEK RS Series User Manual

Page 20

background image

User Manual

AMETEK Programmable Power

RS Series

20

2.1.7 Unit Protection

Input Over current:

In-line fast acting fuses. Check fuse rating in Service and Maintenance section.
Ratings will depend on AC input configuration settings.

Circuit breaker for LV supply.

Input Over voltage:

Automatic shutdown.

Input Over voltage
Transients:

Surge protection to withstand EN50082-1 (IEC 801-4, 5) levels.

Output Over current:

Adjustable level constant current mode with programmable set point.

Output Short Circuit:

Peak and RMS current limit.

Over temperature:

Automatic shutdown.

2.2 Mechanical

Parameter

Specification

Dimensions:
(for each RS chassis)

Height:

74.5”

1892.3 mm

Width:

30.3”

769.6 mm

Depth:

38.3”

972.8 mm

Unit Weight:
(for each RS chassis)

Net:

2150 lbs / 975 Kg approximately

2475 lbs / 1123 Kg approximately including –AV option

Shipping:

2450 lbs / 1111 Kg

approximately

2775 lbs / 1258 Kg approximately including –AV option

Material:

Steel chassis with aluminum panels and covers.

Finish:

Light textured painted external surfaces.

Panels semi-gloss polyurethane color no. 26440 (medium gray)

Cooling:

Fan cooled with air intake on the front and exhaust to the rear.
Fans:

14 x 225CFM.

Air displacement

50 Cu Ft/sec. Max.

Internal Construction:

Modular sub assemblies.

Rear Panel
Connections:

(See section 3 for description of connections)

Cable entry and strain relieve for AC input wiring

Cable entry and strain relieve for output wiring

External sense terminal block (Remote voltage sense)

System interface (2x)

Clock and Lock BNC's (requires -LKM or -LKS options)

RS232, USB, GPIB, LAN (option)

Trigger In BNC

Trigger Out BNC

Function Strobe BNC

Output Status