9.2.- CirLAMP Mode DN
AC power supply
Mode
Self-powered
Rated voltage
184 ... 276 V ~
Frequency
50/60Hz
Consumption
2W 16VA
Installation category
CAT III 300 V
Voltage measurement circuit
Voltage measurement margin
184 to .276 V ~
Input impedance
600 MΩ
Installation category
CAT III 300 V
Current measurement circuit
Current measurement margin
0.1 ... 3A
Minimum measurement current (Istart)
0.08 A
Installation category
CAT III 300 V
Measurement accuracy
Voltage measurement
< 5% of full-scale
Current measurement
< 5% of full-scale
Active and reactive power measurement
< 5% of full-scale
Relay output: Control relay ON/OFF
Maximum voltage, open contacts
250 V ~
Maximum current
10 A
Maximum switching power
2500 W (AC1)
Electrical life (at full load)
100x10
3
cycles
Mechanical life
10x10
6
cycles
Relay outputs: Bi-level control relay
Maximum voltage, open contacts
250 V ~
Maximum current
5 A
Maximum switching power
1250 VA - 150 W
Electrical life (at full load)
1x10
5
cycles
Mechanical life
2x10
7
cycles
PLC (Power Line Communications)
Hardware
CENELEC B DCSK
Baud rate
2400 bauds with repeater management
Protocol
CirPLC (DCSK)
Insulation
AlC voltage
4 kV RMS 50 Hz for 1 minute
Overimpulse
1.2/50 μs 0R source impedance
2 kV UNE-EN 61000-4-5:2007 + CORR:2010
92
CirLAMP system
Instruction Manual